Product brief
FDC-P40-LC: The Liquid-Cooled Container, Spec'd
The liquid-cooled container is the second product in our two-product container line (air + liquid — we don’t sell a hybrid; the reasoning is on the air page and in the three-chain analysis).
Platform (FDC-P40-LC): 40-ft high-cube, LV direct-in, 10–14 rack positions [canon, /products/pod/] — fewer than the air box because a CDU bay and vertical manifold gallery take the space — plus factory cold-plate loop, CDU 2×N (1+1) whole-unit backup: two complete CDUs, sized so one survivor carries the full IT load ×1.1 (2×700 kW for the 630 kW H200 build; 2×850 kW for the 756/770 kW builds) [canon, spec book §3.2], shared tie-bus + isolation valves, UPS-backed pumps and controls, external adiabatic dry-cooler bank — 3–4 large V-coil units (N+1), sized at the Texas triple (42 °C dry bulb / 25 °C wet bulb / glycol), where nameplate output derates to ~69% [est., working paper §5]. PUE 1.15–1.20 [canon], WUE ≈ 0 (refrigerant primary side). Delivery 6–9 months [canon]. Unlike the air box — whose rack-sized DX units eat floor positions — the LC plant is one bay, so nearly every rack position stays IT.
Why the rack count drops and the box still wins: each rack carries 2–2.5× the air box’s load, and each rack holds more servers. Fewer racks, more silicon per container.
The two chip configurations
Servers per rack is a chassis-height fact before it is a thermal choice. 8-GPU HGX nodes ship in 6U–10U chassis; a 42U rack holds 5 × 8U or 6 × 6U (leaving ToR space), so the two configs below differ by more than the chip:
| LC + H200 | LC + H200 (6U variant) | LC + B300 | |
|---|---|---|---|
| Server | H200 cold-plate node, 8U chassis, ~10.5 kW [est.] | H200 cold-plate node, 6U chassis (XE9680-class), ~10.5 kW [est.] | B300 cold-plate node (~10U), ~13.5 kW [est.] |
| GPU TDP | 700 W [fact] | 700 W [fact] | 1,400 W [fact] |
| Servers / rack | 5 | 6 | 4 |
| Rack load | 52.5 kW | 63 kW | 55 kW |
| IT racks used | 12 of 14 | 12 of 14 | 14 of 14 |
| Container IT | 630 kW | 756 kW | 770 kW |
| Tier filled | LC-850 (74%) | LC-850 (89%) | LC-850 (91%) |
| GPUs per container | 480 | 576 | 448 |
| Utility feed at PUE 1.15 | ~0.73 MVA | ~0.87 MVA | ~0.89 MVA |
The Texas plant, sized honestly: the adiabatic bank takes 80–120 m² of pad and runs ~63.5 dB(A) at 10 m ◐ — a night-time 45 dB(A) line wants real setback (~84 m) or a sound screen, so “compact deployment” claims stop at the property line. The adiabatic assist spends a few hundred peak-hours of water a year; fully dry is the default, wet is the 42 °C escape hatch. Sizing math and vendor-curve caveats: the liquid B300 brief.
Every configuration ships with its tier-matched 1+1 CDU pair — pump-level redundancy alone
(factory standard) is not machine-level redundancy: a whole-CDU failure on a pump-only plant
drops the surviving unit far below load within seconds (ASHRAE TC 9.9: ~23 s to processor
throttling, ~2 s ride-through on 45 °C warm water [S1]). With 1+1 the survivor runs the full load,
maintenance windows stay concurrent, and the liquid side stops being the weak tier. The 6U-variant LC + H200 is
the density sleeper — 576 GPUs in one 40-ft box — but it commits you to a 6U chassis at
server selection. The 8U default (480 GPUs) is the safe spec. NVL72-class rack-scale
systems are a separate variant (9–10 racks at ~135–140 kW [fact] fill an LC-1,250),
priced on request.
Choose this box when
- Your GPUs are cold-plate B300 (or you want the density headroom the 1,400 W generation requires).
- Your training economics justify ~2× the silicon per container and you can hold the leak-discipline regime (log every mate/demate, test every sensor) — that’s the kill condition.
- The site has no water to spare — the refrigerant primary loop means zero process water in the machine hall and WUE ≈ 0.
Kill condition
Walk away if the operating team cannot hold leak-discipline. At 55–63 kW/rack there is no graceful version of a manifold failure. For those teams, the air container with air-node B300s is the honest answer at roughly half the density.
Working papers: /solutions/modular-liquid-b300/ · estimate math: /solutions/container-dc-estimator/.